Important update regarding the Condair MLRO
MLRO Submittal Corrections for Inlet Water Requirements
|
TB: 24-07
Date: Monday, July 29th, 2024
Product Lines Affected: MLRO Series Reverse Osmosis Humidifier Water Treatment
|
The current MLRO submittals present a table with information about the water supply.
The current submittals incorrectly state that the flow requirement for standalone units and units paired with pre-treatment are identical. The Kinetico softeners CP210 and C213, when paired use a backflush process in increase unit efficiency.
|
The CP210 softeners require a backwash flow of 3.00 gpm, while the CP213 softeners require a backwash flow of 5.00 gpm. This information was previously shown on the submittals but did not clearly convey the true inlet water flow requirements.
|
The table below displays the revised values that will be displayed on new submittal documents.
|
|
|
If required, the application engineering team (na.applications@condair.com) can provide an updated submittal for use with ongoing projects.
Please contact your local Regional Sales Manager or Kevin Deavy with any questions or concerns.
Sincerely,
Kevin Deavy
Technical Product Manager
Office: +1 613 822 0335
kevin.deavy@condair.com
|
|
|
Manage your preferences | Opt Out using TrueRemove™
Got this as a forward? Sign up to receive our future emails.
View this email online.
|
2740 Fenton Road | Ottawa, ON K1T3T7 CA
|
|
|
This email was sent to .